H05BQ-F and H07BQ-F* (NGMH11YÖ) EPR-insulated power cables with PUR jacket 

TECHNICAL DATA
  • EPR/PUR power cables according to DIN VDE 0282 Part 10 and HD 22.10 S1
  • Temperature range 
    moving –35° C to +80° C
    not moving –45° C to +90° C
  • Permissible operating temperature at the conductor +90° C
  • Rated voltage
    H05BQ-F: U0/U 300/500 V up to 1 mm2
    H07BO-F: U0/U 450/750 V for 1,5 mm2 and more
  • Test voltage
    H05BQ-F: 2000 V up to 1 mm2
    H07BQ-F: 2500 V for 1,5 mm2 and more
  • Minimum bending radius
    freely moving: approx. 5x  cable diameter
    Radiation resistance
    up to 100x 106 cJ/kg (up to 100 mrad)
Particular features
  • Abrasion-resistant
  • Notch ductile
  • Tear- and cut-resistant
  • Good flexibility at low temperatures of up to -40° C
DESCRIPTION
  • Stranded copper wire, bright or tinned, fine wires according to DIN VDE 0295 Kl. 5, BS 6360 cl. 5 or HD 383 Kl. 5
  • Insulating jacket made of rubber, mixture El6 according to DIN VDE 0282 Part 1
  • Wire marking according to DIN VDE 0293
  • Earthed conductor green/yellow outside, for 3 or more wires
  • Wires with optimum lengths of lay stranded in layers (inner protective sleeve permitted)
  • Outside PUR jacket TMPU according to DIN VDE 0282 Part 10, Annex A, jacket colour: orange (RAL 2003), imprint: at least „BQ“
  • The materials used for production are free from silicone and cadmium and free from substances harmful to the protective enamel 
APPLICATION

For medium mechanical loads, these cables may be used in dry, humid or wet rooms, e.g. for the connection of agricultural or commercial equipment and heaters, provided there are no exposed hot parts that can be touched accidentally. These robust, flexible cables are used for electric tools such as drilling machines, circular saws and portable motors and machines in agriculture, at building sites, at yards and for deep-freezing plants.

Resistant to
  • Oil and grease
  • Petrol
  • Water and influences of the weather
  • Ozone and oxygen
  • UV radiation
  • Hydrolysis
  • Microbes
No. of wires
Cross-section mm²
Outer dia. mm
min - max
Copper No.
kg/km
Weight
approx.  kg/km
2 x 0,75 5,7–7,4 14,4 52
3G0,75 6,2–8,1 21,6 63
4G0,75 6,8–8,8 29,0 80
5G0,75 7,6–9,9 36,0, 96
       
2 x 1 6,1–8,0 19,2 59
3G1 6,5–8,5 29,0 71
4G1 7,1–9,3 38,4 89
5G1 8,0–10,3 48,0 112
       
2 x 1,5 7,6–9,8 29,0 92
2 x 2,5 9,0–11,6 48,0 121
       
3G1,5 8,0–10,4 43,0 109
3G2,5 9,6–12,4 72,0 164
       
4G1,5 9,0–11,6 58,0 145
4G2,5 10,7–13,8 96,0 207
       
5G1,5 9,8–12,7 72,0 169
5G2,5 11,9–15,3 120,0 262

CE = The product complies with the EC Low-Voltage Directive 72/23/EWG or 93/68/EWG